SN | Building No. | Unit qty. | Floor qty. | Construction area (m2) | Heating supply area (m2) |
---|---|---|---|---|---|
1 | #1 | 3 | 18 | 23086.5 | 7632.46 |
2 | #2 | 2 | 18 | 9781 | 2337.86 |
3 | #3 | 2 | 18 | 15309.36 | 5181.87 |
4 | #4 | 2 | 18 | 16465.4 | 4188.8 |
5 | #5 | 2 | 12 | 10113.6 | 4194.52 |
6 | #6 | 2 | 18 | 16465.4 | 7502.58 |
7 | #7 | 2 | 18 | 9558.21 | 4501.11 |
8 | #8 | 2 | 11 | 9279.6 | 4254.63 |
9 | #9 | 2 | 16 | 8431.84 | 3394.79 |
Working condition | Unit No. | (sing time)/s | t. (mp. fluctuation range)/°C |
Heat inlet (lower zone) | Valve opening (%) | Supply/return water temp. (°C) | Heat inlet (higher zone) | Valve opening (%) | Supply/return water temp. (°C) |
---|---|---|---|---|---|
Unit 1 Building 1 | 97 | 35.8/32.6 | Unit 1 Building 1 | 97 | 37.2/31.2 |
Unit 2 Building 1 | 97 | 35.5/31.5 | Unit 2 Building 1 | 97 | 35.2/33.6 |
Unit 3 Building 1 | 97 | 35.5/33.7 | Unit 3 Building 1 | 97 | 37.6/35.6 |
Unit 1 Building 2 | 62 | 37.2/34.4 | Unit 1 Building 2 | 65 | 36.8/34.6 |
Unit 2 Building 2 | 57 | 36.2/34.4 | Unit 2 Building 2 | 97 | 37.4/34.8 |
Unit 1 Building 3 | 13 | 37.4/35.3 | Unit 1 Building 3 | 31 | 37.1/34.7 |
Unit 2 Building 3 | 32 | 37.5/35.1 | Unit 2 Building 3 | 31 | 37.4/34.1 |
Unit 1 Building 4 | 22 | 37.6/35.5 | Unit 1 Building 4 | 27 | 36.4/34.8 |
Unit 2 Building 4 | 22 | 37.6/36.1 | Unit 2 Building 4 | 20 | 36.4/34.2 |
Unit 1 Building 5 | 34 | 38.8/36.1 | Unit 1 Building 6 | 52 | 37.1/35.5 |
Unit 2 Building 5 | 55 | 38.5/34.7 | Unit 2 Building 6 | 47 | 37.1/34.6 |
Unit 1 Building 6 | 43 | 39.1/36.3 | Unit 1 Building 7 | 60 | 37.2/35.3 |
Unit 2 Building 6 | 37 | 39.1/36.1 | Unit 2 Building 7 | 16 | 37.4/35.2 |
Unit 1 Building 7 | 45 | 38.3/35.7 | Unit 1 Building 9 | 76 | 37.4/34.7 |
Unit 2 Building 7 | 56 | 38.5/34.6 | Unit 2 Building 9 | 60 | 37.9/32.5 |
Unit 1 Building 8 | 22 | 38/32 | |||
Unit 2 Building 8 | 22 | 37.3/33.5 | |||
Unit 1 Building 9 | 32 | 38.2/31.8 | |||
Unit 2 Building 9 | 55 | 38.4/35.5 |
Unit No. | Controller | Parameters |
---|---|---|
Higher zone, Unit 2, Building 1 | Primary loop |
|
Lower zone, Unit 1, Building 6 | Primary loop |
|
Lower zone, Unit 2, Building 9 | Primary loop |
Heat inlet (lower zone) | Valve opening (%) | Return water temp. (°C) | Heat inlet (higher zone) | Valve opening (%) | Return water temp. (°C) |
---|---|---|---|---|---|
Unit 1 Building 1 | 62 | 35.81 | Unit 1 Building 1 | 95 | 35.82 |
Unit 2 Building 1 | 56 | 36.14 | Unit 2 Building 1 | 86 | 35.36 |
Unit 3 Building 1 | 54 | 35.74 | Unit 3 Building 1 | 89 | 36.26 |
Unit 1 Building 2 | 31 | 35.95 | Unit 1 Building 2 | 24.8 | 35.76 |
Unit 2 Building 2 | 22 | 36.36 | Unit 2 Building 2 | 24 | 35.65 |
Unit 1 Building 3 | 20.6 | 35.55 | Unit 1 Building 3 | 26 | 35.67 |
Unit 2 Building 3 | 24 | 35.85 | Unit 2 Building 3 | 28 | 35.66 |
Unit 1 Building 4 | 12.6 | 36.12 | Unit 1 Building 4 | 20.8 | 36 |
Unit 2 Building 4 | 18 | 35.62 | Unit 2 Building 4 | 19 | 35.51 |
Unit 1 Building 5 | 24.8 | 35.73 | Unit 1 Building 6 | 24 | 35.92 |
Unit 2 Building 5 | 26 | 35.84 | Unit 2 Building 6 | 18 | 35.44 |
Unit 1 Building 6 | 14 | 36 | Unit 1 Building 7 | 22 | 35.75 |
Unit 2 Building 6 | 14 | 36.56 | Unit 2 Building 7 | 22 | 35.6 |
Unit 1 Building 7 | 28 | 36.1 | Unit 1 Building 9 | 12 | 36.1 |
Unit 2 Building 7 | 38 | 35.86 | Unit 2 Building 9 | 16 | 36.22 |
Unit 1 Building 8 | 33 | 35.56 | |||
Unit 2 Building 8 | 22 | 35.82 | |||
Unit 1 Building 9 | 16 | 35.78 | |||
Unit 2 Building 9 | 26 | 35.59 |
Input | Output | ||
---|---|---|---|
I0.0 | System On | Q0.0 | Automatic operation indicator |
I0.1 | System Off | Q0.1 | Comprehensive alarm indicator |
I0.2 | Manu/Auto switchover | Q0.2 | Out-of-control valve in unit #1 higher zone |
I0.3 | Emergency cut-off | Q0.3 | Out-of-control valve in unit #1 lower zone |
AIW16 | Return water temperature in unit #1 higher zone | Q0.4 | Out-of-control valve in unit #2 higher zone |
AIW18 | Return water temperature in unit #1 lower zone | Q0.5 | Out-of-control valve in unit #2 lower zone |
AIW20 | Return water temperature in unit #2 higher zone | Q0.6 | Return water temperature alarm in unit #1 |
AIW22 | Return water temperature in unit #2 lower zone | Q0.7 | Return water temperature alarm in unit #2 |
AIW24 | Supply water pressure in unit #1 higher zone | Q1.0 | Supply and return pressure difference alarm in unit #1 |
AIW26 | Return water pressure in unit #1 higher zone | Q1.1 | Supply and return pressure difference alarm in unit #2 |
AIW28 | Supply water pressure in unit #1 lower zone | AQW48 | #1 Higher valve opening instruction |
AIW30 | Return water pressure in unit #1 lower zone | AQW50 | #1 Lower valve opening instruction |
AIW32 | Supply water pressure in unit #2 higher zone | AQW52 | #2 Higher valve opening instruction |
AIW34 | Return water pressure in unit #2 higher zone | AQW54 | #2 Lower valve opening instruction |
AIW36 | Supply water pressure in unit #2 lower zone | ||
AIW38 | Return water pressure in unit #2 lower zone | ||
AIW40 | Valve feedback in unit #1 higher zone | ||
AIW42 | Valve feedback in unit #1 lower zone | ||
AIW44 | Valve feedback in unit #2 higher zone | ||
AIW46 | Valve feedback in unit #2 lower zone |