Otwarty dostęp

FIRE SAFETY IN THE BUILT-ENVIRONMENT: A CASE STUDY IN A RESIDENTIAL FACILITY


Zacytuj

Figure 1.

Floor plan of the case study building
Floor plan of the case study building

Figure 2.

Elevation views of the case study building
Elevation views of the case study building

Code-compliance checklist for fire safety requirements in residential facilities

  A. Means of egress Yes No
1. Exits are not to be less than the required number and capacity as per the code.
2. Exit doors are swinging in the direction of egress.
3. The travel distance does not exceed 15 meters.
4. Exterior doors are leading to discharge outside the building, or a public path.
5. Corridors are always lighted when the building is occupied.
6. Exit signs are available, and lighted throughout the building.
7. There are no barriers that would reduce the width of any exit.
8. The phrase “PUSH TO EXIT” is available on all fire doors.
9. Exit lighting could be operated using a standby power supply in case of an absence of municipal power supply.
  B. Fire protection systems
10. An automatic sprinkler system is installed throughout all floors.
11. Fire extinguishers are placed every 22 meters, in visible locations.
12. Fire extinguishers are mounted on walls.
13. Fire extinguishers are inspected annually.
14. There is no paint over sprinkler heads, except that of the factory.
15. Records of fire protection systems’ inspections are kept for the past 3 years.
16. A 1 meter net space is provided around every fire hydrant.
17. Fire alarms are provided throughout the building.
  C. Electrical installation and distribution systems
18. Power taps are directly plugged into permeant sockets.
19. Relocatable cords are not passing through interior walls, finished floors, ceilings, doors or floor finishes, and are not subjected to harm.
20. Extension cords are not an alternative to permanent wiring.
21. Extension cords are not damaged.
22. There are no open junction boxes, as well as open wiring connections.
23. Electrical motors do not have any accumulations of oil or dirt.
24. The phrase “ELECTRICAL ROOM” is available on all doors of electrical rooms.
  D. Fire doors
25. Fire doors are not blocked in any way.
26. The assemblies of fire doors are not modified in any way.
27. Fire doors’ closers have enough force to close and latch the door.
28. Fire doors remain in closed positions at all times.
  E. Housekeeping practices
29. Storage containing combustibles are kept in an organized manner.
30. The storage space is isolated from heat sources.
31. There are no combustibles stored in exits, exit enclosures, boiler, mechanical, and electrical rooms.
32. Dumpsters and containers are adequately provides throughout the building.
  F. Miscellaneous fire safety requirements
33. The building has a clear, readable address number.
34. Accessibility to the fire hydrant are not obstructed in any way.
35. Evacuation plans are clearly posted throughout the building.
  G. Hazardous materials
36. Flammable liquids are not available in the basement.
37. There are no more than 10 gallons of flammable and combustible liquids used for operation and maintenance of equipment.
38. There is no excessive storage of gas containers throughout the building.
eISSN:
1899-0142
Język:
Angielski
Częstotliwość wydawania:
4 razy w roku
Dziedziny czasopisma:
Architecture and Design, Architecture, Architects, Buildings