Method for Increasing Sensitivity of the Distance Protection on a 330 KV Double-Circuit Transmission Line
, , y
10 feb 2011
Acerca de este artículo
Publicado en línea: 10 feb 2011
Páginas: 15 - 24
DOI: https://doi.org/10.2478/v10047-010-0021-2
Palabras clave
This content is open access.
Possibilities of increasing the distance protection (DP) sensitivity are considered for a double-circuit transmission line connected to a substation busbar only with one circuit-breaker in each phase. The DP sensitivity can be increased on such a line using mutual connections of the phase wires along its whole length. The minimal (optimal) number of the connections is found by the proposed calculation method.