Figure 1.

The SketchUp model of the building – view from the south façade
The SketchUp model of the building – view from the south façade

Figure 2.

Maximum, average and minimum temperature in individual months for weather data adopted for simulation
Maximum, average and minimum temperature in individual months for weather data adopted for simulation

Figure 3.

Pareto Front: a) brick standard building, b) wood standard building, c) brick passive building, d) wood passive building
Pareto Front: a) brick standard building, b) wood standard building, c) brick passive building, d) wood passive building

Temperature set-point for heating

Room Temperature (operating time)
Garage 8°C (0:00-24:00)
Vestibule and Utility room 16°C (0:00-24:00)
Bathrooms 24°C (6:00-24:00) 18°C (24:00-6:00)
Living-room with kitchen, Hall, Study, Bedroom, Child’s rooms 21°C (6:00-24:00) 18°C (24:00-6:00)

Effective leakage area assumed to simulations

Thermal zone Length of the window leakages, m Number of air inlets Number of ventilation ducts Flow coefficient for window, m3/(hPa0.67) Effective leakage area, cm2
Living room with kitchen 43.8 5 1 13.1 111
Bathroom on ground floor - - 1 - 29
Utility room 10.7 1 1 3.2 47
Garage 9.2 0 1 9.2 54
Study 6.6 1 0 2.0 15
Bedroom 13.2 2 0 4.0 29
Child’s rooms 22.4 4 0 6.7 55
Bathrooms on 1st floor 4.6 1 3 1.4 100
Hall 4.6 1 0 1.4 13

Percentage share of discomfort hours compared to all occupied hours in rooms

Building case Criterion Max air change rate in the rooms due to windows opening, h-1 Hdis, %
annual summer
max avg max avg
Brick standard insulated building KQ 47.7 26.9 98.0 74.8
KU 3.5 13.7 4.2 40.6 12.6
KH 9.8 1.5 0.7 4.8 0.9
Wood standard insulated building KQ 47.7 30.1 91.7 76.7
KU 3.5 21.3 7.7 51.0 19.8
KH 8.5 5.2 2.6 13.2 4.9
Brick passive insulated building KQ 54.8 42.8 100 100
KU 7.8 17.7 8.6 43.6 24.7
KH 9.8 5.1 1.9 12.0 4.9
Wood passive insulated building KQ 56.0 43.2 100 100
KU 4.4 30.8 17.1 62.8 45.6
KH 8.4 14.6 5.8 33.9 13.7

Maximum, average and minimum indoor temperature for KU solution (summer period)

Building case Temperature, ° C
Study Child ’ s rooms Living-room Bedroom
Brick standard insulated building max 32.5 30.8 32.2 31.5
min 21.8 22.5 21.5 22.2
avg 26.7 26.7 26.1 26.6
Wood standard insulated building max 33.7 32.6 33.5 33.4
min 19.4 20.5 20.5 21.0
avg 26.6 26.7 26.1 26.6
Brick passive insulated building max 33.0 31.4 34.4 32.3
min 21.6 22.9 21.3 21.4
avg 26.7 27.1 27.1 26.7
Wood passive insulated building max 34.5 33.9 36.6 34.7
min 20.3 21.1 20.7 20.5
avg 27.3 27.7 28.0 27.3

Objective function results for optimal solutions

Building case Criterion Qheat, kWh Hdis, h
Brick standard insulated building KQ 5469 3397
KU 5584 533
KH 5873 91
Wood standard insulated building KQ 5726 3801
KU 5839 976
KH 6074 344
Brick passive insulated building KQ 2924 5411
KU 3151 1085
KH 3491 247
Wood passive insulated building KQ 3210 5445
KU 3381 2164
KH 3714 741
eISSN:
1899-0142
Idioma:
Inglés
Calendario de la edición:
4 veces al año
Temas de la revista:
Architecture and Design, Architecture, Architects, Buildings