RESEARCH OF SINGLE ROOM DECENTRALIZED HEAT RECOVERY UNIT
, und
07. Jan. 2020
Über diesen Artikel
Artikel-Kategorie: research-article
Online veröffentlicht: 07. Jan. 2020
Seitenbereich: 109 - 114
Eingereicht: 28. Juli 2019
Akzeptiert: 02. Okt. 2019
DOI: https://doi.org/10.21307/acee-2019-056
Schlüsselwörter
© 2019 Piotr KOPER et al., published by Sciendo
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Figure 1.
![HRU-WALL-100-25 compact recuperator and its dimensions in millimeters [11]](https://sciendo-parsed.s3.eu-central-1.amazonaws.com/64706f9983f1392090d697be/j_acee-2019-056_fig_001.jpg?X-Amz-Algorithm=AWS4-HMAC-SHA256&X-Amz-Content-Sha256=UNSIGNED-PAYLOAD&X-Amz-Credential=AKIA6AP2G7AKOUXAVR44%2F20250907%2Feu-central-1%2Fs3%2Faws4_request&X-Amz-Date=20250907T184156Z&X-Amz-Expires=3600&X-Amz-Signature=97312917763b9e8d8fd41d3892f11b2e30ae84ae3025dfe4e8edc2f9d0201af6&X-Amz-SignedHeaders=host&x-amz-checksum-mode=ENABLED&x-id=GetObject)
Figure 2.

Figure 3.

Figure 4.

Figure 5.

Figure 6.

Figure 7.

Calculated averaged air flow volume rate for all fan speeds based on measurements for 0 Pa
Air supply | 0 Pa |
---|---|
first fan speed | 9 m3/h |
second fan speed | 16 m3/h |
third fan speed | 28 m3/h |
Air exhaust | 0 Pa |
first fan speed | 8 m3/h |
second fan speed | 14 m3/h |
third fan speed | 29 m3/h |
Calculated supply efficiency for the tested working conditions
Working conditions | Supply efficiency |
---|---|
third fan speed at balanced pressures | 64% |
second fan speed at balanced pressures | 68% |
first fan speed at balanced pressures | 79% |
third fan speed at a natural pressure difference | 56% |
second fan speed at a natural pressure difference | 47% |
Calculated exhaust efficiency for the tested working conditions
Working conditions | Exhaust efficiency |
---|---|
third fan speed at balanced pressures | 73% |
second fan speed at balanced pressures | 83% |
first fan speed at balanced pressures | 85% |
third fan speed at a natural pressure difference | 79% |
second fan speed at a natural pressure difference | 93% |
Calculated averaged air flow volume rate for all fan speeds based on measurements for 7 Pa
Air supply | 7 Pa |
---|---|
first fan speed | 19 m3/h |
second fan speed | 22 m3/h |
third fan speed | 36 m3/h |
Air exhaust | 7 Pa |
first fan speed | -8 m3/h |
second fan speed | 6 m3/h |
third fan speed | 25 m3/h |
Calculated averaged air flow volume rate for all fan speeds based on measurements for 4 Pa
Air supply | 4 Pa |
---|---|
first fan speed | 14 m3/h |
second fan speed | 20 m3/h |
third fan speed | 32 m3/h |
Air exhaust | 4 Pa |
first fan speed | 2 m3/h |
second fan speed | 12 m3/h |
third fan speed | 27 m3/h |