Impact of Water Mist Extinguisher Construction on Parameters of Generated Drops
Article Category: research-article
Published Online: Jan 27, 2021
Page range: 99 - 104
Received: Oct 30, 2020
Accepted: Nov 23, 2020
DOI: https://doi.org/10.21307/acee-2020-034
Keywords
© 2020 Jan Kaźmierak published by Sciendo
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
The paper analyses the impact that the construction of water mist extinguishers exerts on the size of generated drops. The test was based on the examination of three extinguishers of two producers, which have been available in the market in recent years.
The test was carried out with the use of the IPS Drop Spectrum Analyzer (DSA). The device operates by using the photoelectric method to measure the parameters of the extinguishing stream microstructure. There were two measuring ranges: 0÷1 414 µm and 0÷2 658 µm.
The test results present mean diameters of the generated drops, aggregated curves representative of their share as well as the analysis of the quality of spraying the extinguishing medium. The tests have shown that two out of three tested extinguishers do not generate water mist with standard parameters at a distance of 170 cm. The smallest mean diameters of drops were generated by extinguisher B, whereas the biggest ones by extinguisher C The highest level of spraying among all samples was found for extinguisher B. It’s Sauter diameter mean amounted to 564.03 µm. Further, it was shown what impact the construction of water mist extinguishers exerts on the size of generated drops.