ANTI-WINDUP STRATEGY FOR AN LQ CURRENT CONTROLLER WITH OSCILLATORY TERMS FOR THREE-PHASE GRID-TIE VSCs IN SMES SYSTEMS
, , , e
27 ott 2017
INFORMAZIONI SU QUESTO ARTICOLO
Pubblicato online: 27 ott 2017
Pagine: 65 - 81
Ricevuto: 25 ott 2016
Accettato: 14 dic 2016
DOI: https://doi.org/10.5277/ped160204
Parole chiave
© 2017
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 License.
The paper presents a linear-quadratic current controller with damped oscillatory terms designed for three-phase grid-tie voltage source converters used in SMES systems and operated under distorted grid voltage conditions. Special emphasis is placed on a synthesis of an anti-windup mechanism to prevent wind-up derived from the oscillatory terms by the use of a new active damping loop based on a simple moving average method. As a consequence, the current feedback gain may be increased without unwanted overshoot and overruns, and performance of the system can be improved.