Analysis of the Impact of Unbalanced Connection of Consumers and Electric Vehicles on Voltage Variation and Voltage Unbalance
Categoria dell'articolo: Original scientific paper
Pubblicato online: 22 giu 2024
Pagine: 1 - 11
Ricevuto: 10 gen 2024
Accettato: 27 mag 2024
DOI: https://doi.org/10.2478/bhee-2024-0001
Parole chiave
© 2024 Jasmina Bešić et al., published by Sciendo
This work is licensed under the Creative Commons Attribution 4.0 International License.
Voltage unbalance and voltage variations are common issues in low voltage distribution networks caused by unbalanced connection of single-phase loads and electric vehicles (EVs) among phases. Part of the real low voltage grid in Bosnia and Herzegovina, in the vicinity of the town of Tešanj, was analysed. The impact on single-phase consumer and single-phase EVs penetration was analysed. The grid was modelled using DIgSILENT PowerFactory software. Three cases of the distribution of consumers by phases were analysed. Each of the three cases is expanded with four scenarios depending on the penetration of EV into the grid. Results showed that none of the twelve scenarios remained within the permissible limits of −10% voltage variation limit of EN 50160 for phase A. Seven of the twelve scenarios exceeded voltage unbalance limits +2% according to EN 50160.