Static load test is a method that most accurately describes the operating conditions of the pile. During the test, settlement of pile head corresponding to the degree of load was measured. It gives a set of points {
The formation of the skin friction and the resistance under the toe of the pile is very important, because this information is essential for pile design. It turns out that the rate of skin friction mobilisation and resistance under the toe of the pile are completely different. Moreover, the maximum values of skin friction and toe resistance are mobilised at different settlement value. The resistance distribution in an ultimate limit state, which is the basis of the design method, may be completely different from the resistance distribution in the real conditions of pile–soil interaction. Conclusions similar to that were also received by Krasiński, Gwizdała [3], Salgado and Prezzi [7].
Axially loaded pile transmits forces by the skin friction and the soil resistance under the toe of the pile. It is absolutely obvious. The question is: what is the participation of skin friction and toe resistance in distribution load? Can we interpret these two values independently? To find the answer to these questions, a series of laboratory experiments have been conducted. The research have included static load tests of model concrete pile with a diameter of 7 cm, and length of 20 cm with appropriate measurement instrumentation to record the resistance under the toe of the pile. Pile was embedded in non-cohesive, homogeneous soil.
The study was conducted on laboratory model of pile in reduced scale. The relationship between the diameter and length of the pile is not directly proportional, but the soil behaviour because of ultimate strength is similar to real pile–soil behaviour. The laboratory test stand consisted of steel chamber, which was 48.5 cm in diameter and 60 cm in height. The chamber was filled with non-cohesive soil (medium sand). Pile model with a diameter of 7 cm and height of 30 cm was made of concrete. The toe and the head of the pile were specially constructed. Force sensors that measured the load distribution during static load test were installed (Fig. 1). The settlement of the head of the pile, within a range of 0–15 mm, was measured by linear potentiometer installed on independent base. The load was applied using elevating cylinder. The results were read out by data logger connected to a computer. The instrumented pile was calibrated in testing machine under vertical compression load.
The soil was placed layer by layer in a chamber and dynamically compacted using 15-kg steel plate. Water content in the soil is about 2–3%. During filling, the density of the sand was measured. In this way, the density was determined in 3 places in the chamber. In addition, after filling the chamber, the relative density of the sand was determined. Next the hole in the soil was made using tube and the pile was inserted. The soil in the 1–2 mm slot surrounding the shaft of the pile was compacted. Afterwards, the sensors and elevating cylinder were set. Finally, we obtained a pile embedded in the soil without influence on the soil structure so we cannot compare this pile to displacement pile, rather to the boring pile.
The research enabled static pile load test. During loading, the settlement and forces of the head and at the toe were measured. The constant load lasted until the stabilisation of the settlement of the pile head. The study was conducted until the 15-mm settlement was achieved. After the test, the stress of soil under the pile base had exceeded the ultimate values. More details about it can be found in a book about non-cohesive soil mechanics by Sawicki [8]. To carry out next test, it was necessary to empty the chamber and fill it again because the destroyed structure of the soil could have a significant impact on the results. In the laboratory of the Department of Geotechnical Engineering, 8 static pile load tests were conducted. Instrumented pile prepared for testing is presented in Figures 2 and 3. In the appropriate mathematical description term appears H/D, which is a scale parameter. The laboratory tests were made for 2.5<H/ D<9; however, in the presented article, the description is given only for chosen H/D = 2.86.
The results of this study are the settlement of the pile, the force applied in the head of the pile and the force mobilised under the toe of the pile. The findings are presented in Figure 4. Each load step gives two pair of points (
where
The approximation consisted of numerical searching for
where Δ = (
For a set of {
Comparison of the M-K approximation of piles 1 and 8.No Diameter D (m) Depth H (m) M-K approximation parameters 1 0.07 0.20 0.4317 6.66 0.332 0.5362 6.28 0.288 8 0.07 0.25 0.2079 14.69 0.348 0.28335 14.33 0.238
Comparison of the M-K approximation of piles 1 and 8 in experiments.No Diameter D (m) Length H (m) Approximation M-K Calculation 1 0.07 0.20 0.4317 6.66 0.332 0.54848 6.59 0.275 8 0.07 0.25 0.2079 14.69 0.348 0.27192 14.48 0.288
In the further analysis, we concluded the relationship between parameters
Formulas (3–5) allow us to calculate the parameters of resistance under the toe curve based on the parameters obtained from static load test.
Good approximation on
To determine the components of formula 6, we presented it as equation (7).
Constants
we have equation (8).
The set of equation (8) was solved based on date:
For bearing capacity of the pile, we received the following formula (10):
The parameter
Static load test of pile in field tests usually consist of 8 steps of load from force 0 kN to force equals 150% of designed bearing capacity of the pile. The settlement that is stabilised in each step of test and the applied load are recorded. At the end, we have the relationship between settlement and applied load, which is called as a settlement curve. Following the M-K method, we receive 3 parameters:
On the basis of the parameters
Interpreting Figures 7 and 8, we can notice the extremum point of skin resistance and settlement. According to EC7, ultimate settlement equals 10% of diameter of the pile. In laboratory case, it equals 7 mm. During the laboratory tests, the maximum of skin resistance was mobilised in barely 3 mm of settlement. It should be stressed that the bearing capacities are not the ultimate values. The laboratory test verified the relations. The knowledge of skin and toe resistance mobilisation can be used for the improvement at design procedure of pile capacity.
The presented laboratory test verified the possibility of drawing the relationship between the M-K parameters from static load test and skin resistance mobilisation following the settlement.
The figure of skin resistance mobilization indicated the maximum resistance reached at defined settlement. Further increase in settlement resulted in decrease of the skin resistance. It is the aim of further analysis.
In practice, the presented method allows to not only determine the ultimate resistances but also extract the proper value of skin and toe resistance corresponding to the settlement. It may be more rational way in pile capacity designing.