Electric cables can contribute to the spread of fire through the insulating layer. This paper focuses on their properties characterizing the initiation of fire. Samples of ethylene-based cable insulation were tested using a cone calorimeter by exposing them to external heat flows of six different values (25 kW m−2 – 50 kW m−2). Time to initiate flame burning was observed. The critical heat flux (depending on the method of calculation was in the range 2.94 kW m−2 – 4.59 kW m−2) and the thermal response parameter (342 kW s−0.5 m−2) was calculated from the time of initiation and external heat flow dependence.