The Influence of Compensatory Regime of Operation of Pump Hydropower Plant Capljina on Voltage Conditions in Electric Power System of Bosnia and Herzegovina
, , , et
26 oct. 2022
À propos de cet article
Publié en ligne: 26 oct. 2022
Pages: 86 - 94
Reçu: 01 oct. 2021
Accepté: 01 nov. 2021
DOI: https://doi.org/10.2478/bhee-2021-0022
Mots clés
© 2021 Senad Hadžić et al., published by Sciendo
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 3.0 License.
The paper presents the results of testing the operational capabilities of the pump hydropower plant (PHPP) Capljina in compensatory, under excited mode in real time, and answers the questions how, and to what extent, the operation of PHPP Capljina in the under excited mode affects the improvement of voltage conditions in the power system of B&H. The test was performed with one machine in compensatory under excited mode with the takeover of reactive power in the amount of 160 MVAr, in a period of 4 hours. During the test, thermal power plant (TPP) Gacko operated in the maximum under excited mode for a certain period of time.