Analysis of Power Failure with the Phenomenon of an Electric arc in the Electric Power Facility
, y
01 nov 2022
Acerca de este artículo
Publicado en línea: 01 nov 2022
Páginas: 61 - 68
Recibido: 01 sept 2019
Aceptado: 01 jul 2020
DOI: https://doi.org/10.2478/bhee-2020-0014
Palabras clave
© 2020 Ninoslav Simić et al., published by Sciendo
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 3.0 License.
This paper describes cause and effect of an electrical arc fault in industrial TS 6/0.4 kV. Results of insulation resistance test, dielectric withstand test, thermographic inspection, testing of LV installation, as well as recorded data analysis are presented in detail and an events explanation is given. The aim of this paper is to show the purpose of complex testing, both during the events of the accident and during the preventive maintenance. It has also been recommended to analyse calculations of short-circuit currents and the effect of an electric arc on the staff in power facilities, the so-called “arc flash”.