Survey point | Heat source Well | Well 7–Well 9 | Well 9–Well 11 | Well 11–Number 11 Station | Number 11 Station Well 87 | Well 87–Well 21 | Well 21–Number 1 Station | Well 21–Well 23 | Well 23–Number 16 Station | Well 125–Number 34 Station |
Pipe length/m | 2803 | 913 | 642 | 800 | 675 | 1500 | 312 | 300 | 1912 | 249 |
Pipe diameter/mm | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 200 | 900 | 200 | 250 |
Entrance temperature/°C | 80.60 | 80.31 | 80.22 | 80.15 | 80.00 | 79.89 | 79.63 | 79.63 | 79.57 | 79.53 |
Exit temperature/°C | 80.31 | 80.22 | 80.15 | 80.00 | 79.89 | 79.63 | 79.3 | 79.57 | 67.2 | 78.9 |
Entrance enthalpy/J | 337.97 | 336.75 | 336.37 | 336.08 | 335.45 | 334.99 | 333.9 | 333.86 | 333.61 | 333.61 |
Exit enthalpy/J | 336.75 | 336.37 | 336.08 | 335.45 | 334.99 | 333.90 | 332.52 | 333.65 | 281.27 | 330.84 |
Flow/m3/h | 3893.70 | 3893.70 | 3893.70 | 3893.70 | 3893.70 | 2453.88 | 97.8 | 2356.08 | 14.08 | 46.94 |
Density of the heat flow/W/m2 | 136.29 | 130.33 | 141.45 | 246.60 | 213.40 | 143.40 | 147.18 | 145.9 | 131.14 | 139.99 |
Excessive rate of the heat dissipation | −12.99 | −18.16 | −8.87 | 37.55 | 27.84 | −7.39 | −4.63 | 300 | −17.43 | −10.01 |
External surface temperature of equipment, pipes and accessories/K(°C) | 323 (50) | 373 (100) | 423 (150) | 473 (200) | 523 (250) | 573 (300) |
Maximum allowable heat loss/(W/m2) | 104 | 147 | 183 | 220 | 251 | 272 |