Acerca de este artículo
Publicado en línea: 04 may 2019
Páginas: 36 - 42
DOI: https://doi.org/10.1515/sbeef-2019-0008
Palabras clave
© 2019 D. Puiu et al., published by Sciendo
This work is licensed under the Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
The power cables passing through penetration leads to growth of the thermal ageing mechanisms rate. The paper presents the results of the laboratory tests when the real environmental service conditions for penetration are simulated comparison with the result of the thermal computation of the power cables heating and of the temperature influence evaluation of temperature increase of the power cable components on the cable lifetime. For this particular case, a power cable with PVC insulation, we estimated a lifetime decrease about 20 years referring to lifetime (30÷40 years) for location in air.