Enhancing Power Quality in Grid-Integrated Hybrid Renewable Energy System using ANFIS-FBSO
29. Juli 2025
Über diesen Artikel
Artikel-Kategorie: Special issue paper
Online veröffentlicht: 29. Juli 2025
Seitenbereich: 189 - 209
Eingereicht: 30. Apr. 2025
Akzeptiert: 09. Juli 2025
DOI: https://doi.org/10.2478/pead-2025-0014
Schlüsselwörter
© 2025 Manpreet Singh et al., published by Sciendo
This work is licensed under the Creative Commons Attribution 4.0 International License.
Figure 1.

Figure 2.

Figure 3.

Figure 4.

Figure 5.

Figure 6.

Figure 7.

Figure 8.

Figure 9.

Figure 10.

Figure 11.

Figure 12.

Comparison of computational time_
Techniques | Proposed technique (ANFIS-FBSO) | CFA-ANFIS ( |
PSO-ANFIS ( |
EHO-FUZZY ( |
GWO-FUZZY ( |
ASO ( |
---|---|---|---|---|---|---|
Execution time (ms) | 480 | 497 | 510 | 510 | 514 | 590 |
THD comparison between existing and proposed method_
Method | THD level |
||||||||
---|---|---|---|---|---|---|---|---|---|
5 | 7 | 11 | 13 | 17 | 19 | 23 | 25 | 29 | |
Proposed system without compensation | 25 | 29 | 23 | 49 | 19 | 9 | 20 | 9 | 5 |
Proposed technique (ANFIS-FBSO) | 10 | 4 | 2 | 4 | 8 | 2 | 4 | 1 | 0 |
CFA-ANFIS ( |
8 | 8 | 3 | 5 | 10 | 4 | 5 | 6 | 2 |
PSO-ANFIS ( |
14 | 8 | 4 | 7 | 13 | 3 | 8 | 4 | 2 |
EHO-FUZZY ( |
23 | 15 | 16 | 20 | 9 | 7 | 6 | 4 | 4 |
GWO-FUZZY ( |
36 | 10 | 12 | 19 | 10 | 5 | 5 | 3 | 2 |
ASO ( |
12 | 6 | 3 | 5 | 10 | 3 | 5 | 0 | 1 |
Characteristics of proposed technique_
Parameters | Techniques | Values |
---|---|---|
Nominal voltage | Battery | 26.4 V |
Rated capacity | 6.6 Ah | |
Discharge current | 2.86 A | |
Voltage at open-circuit conditions | PV | 64.2 V |
Current at short circuit conditions | 5.96 A | |
Voltage at maximum power point | 54.7 V | |
Current at maximum power point | 5.58 A | |
Maximum value of current | WT | 19 A |
Maximum value of voltage | 500 V | |
Number of membership functions | ANFIS | 5 |
Membership function | Gaussian bell | |
No. of populations | FBSO | 50 |
No. of iterations | 50 |