Uneingeschränkter Zugang

Annual maintenance mode of converter station and preventive test method of DC equipment

, , ,  und   
19. März 2025

Zitieren
COVER HERUNTERLADEN

Figure 1.

The port capacitor affects the voltage simulation model
The port capacitor affects the voltage simulation model

Figure 2.

RL charging single circuit principle diagram
RL charging single circuit principle diagram

Figure 3.

The wiring diagram of the bridge
The wiring diagram of the bridge

Figure 4.

Interference signal caused by vibration
Interference signal caused by vibration

Figure 5.

Local discharge detection signal
Local discharge detection signal

Figure 6.

The time and frequency domain waveform of the mixing bureau
The time and frequency domain waveform of the mixing bureau

Figure 7.

Local discharge signal after processing
Local discharge signal after processing

Figure 8.

Local discharge waveform
Local discharge waveform

Time compared

Stay position Conventional method(s) Ours(s)
1 74.16 39.88
2 83.32 24.30
3 78.65 34.08
4 82.99 34.48
5 81.97 35.26
6 75.21 25.20
7 71.89 36.09
8 77.80 34.65
9 76.79 29.25
10 82.78 37.22
11 80.09 39.92
12 79.28 25.91
13 68.79 32.95
14 78.46 37.00
15 80.06 21.51
16 75.93 35.46
17 81.16 34.96
18 81.10 35.99
19 80.19 37.18
20 80.86 31.93
21 68.54 31.11

Simulation results

Measuring object Cx1 Cx2 Cx3 Cx4
HV LW LW LW LW
GD VM CC+CL LW CC+CL
GND TK TK TK TK
MU CC+CL VM CC+CL LW
Cx/nF 22.17 5.47 2.46 5.53
tan δ / % 0.198 0.147 0.169 0.146
C0 / nF (Theoretical value) 22.21 5.49 2.48 5.54
tan δ / % (Theoretical value) 0.197 0.146 0.167 0.145

Actual measurement results

Measuring object Cx1 Cx2 Cx3 Cx4
HV LW LW LW LW
GD VM CC+CL LW CC+CL
GND TK TK TK TK
MU CC+CL VM CC+CL LW
Cx/nF 25.36 3.74 6.43 3.71
tan δ / % 0.273 0.139 0.243 0.138
C / nF (Theoretical value) 25.32 3.75 6.44 3.72
tan0 δ / % (Theoretical value) 0.271 0.140 0.244 0.139

Comparison of test results

Stay position Factory value(mΩ) Conventional method(mΩ) Ours(mΩ)
1 83.69 68.94 84.11
2 87.2 72.28 81.41
3 81.69 60.07 81.4
4 80.03 68.48 81.29
5 84.65 65.73 85.35
6 84.61 65.07 83.39
7 81.59 61.49 88.3
8 84.29 68.5 81.88
9 89.27 70.43 82.36
10 81.95 68.61 80.8
11 85.14 61.17 84.74
12 86.38 74.33 80.48
13 81.06 61.56 89.67
14 88.5 73.77 85.23
15 88.48 74.69 85.55
16 86.3 69.87 81.27
17 82.41 68.43 81.43
18 83.47 72.84 80.75
19 81.61 71.56 89.81
20 89.94 72.67 86.61
21 82.6 70.68 81.37

The size of equalizing ring of different voltage grades

Voltage rating(kV) Double ring type(mm) Hemispherical form(mm)
d H D
110 150 680 550 480
220 200 890 720 710
500 250 1130 1480 1420
800 300 1560 1690 1630

Local discharge detection results

Group number Local discharge azimuth/° Measured result/° Error/°
1 (88.2,29.3) (87.9,29.1) (0.3.0.2)
2 (88.1,29.1) (0.1,0.2)
3 (87.8,28.9) (0.4,0.4)
4 (87.9,28.8) (0.3,0.5)
5 (88.0,29.2) (0.2,0.1)
6 (87.7,29.2) (0.5,0.1)
7 (88.1,29.0) (0.1,0.3)
8 (88.0,29.1) (0.2,0.2)
Sprache:
Englisch
Zeitrahmen der Veröffentlichung:
1 Hefte pro Jahr
Fachgebiete der Zeitschrift:
Biologie, Biologie, andere, Mathematik, Angewandte Mathematik, Mathematik, Allgemeines, Physik, Physik, andere